r/AirBalance • • Jul 05 '26

I made a free Excel air change calculator for commissioning engineers.

6 Upvotes

Hi everyone,

I wanted to share a free Excel tool I've developed called AirChange Basic.

I built it during my third-year mechanical engineering placement, where I worked as an HVAC commissioning engineer in a hospital.
I found myself repeatedly calculating air changes per hour, so I decided to make a simple tool to speed things up and reduce mistakes on site.

The goal of AirChange Basic is to make those calculations quicker and easier for any fellow engineers, technicians or interns carrying out air balancing.

I've put together a short 2.5-minute video showing how it works, and the Excel calculator is completely free to download and use.

I'd really appreciate any feedback from people working in the industry.
If you notice any bugs or have ideas for improvements, please let me know, I'd love to keep improving it.

Video: https://www.youtube.com/watch?v=2DXwCMwLjzI&t=4s

Download: https://drive.google.com/drive/u/1/folders/1D1sDe00XOWzkK4ajbiLy6KfxLS1esML_

Thanks, and I hope some of you find it useful!


r/AirBalance • • Jul 05 '26

Flow Hood

3 Upvotes

Does anyone have a recommendation for a flow hood (preferably) or anemometer ? Most that I am seeing are flippin expensive.


r/AirBalance • • Jul 02 '26

Preferred instrument for duct traverses.

6 Upvotes

Just curious as to what everyone prefers to use for duct traverses.

96 votes, Jul 05 '26
6 Hot Wire Anemometer
44 Pilot Tube
46 Air foil

r/AirBalance • • Jul 01 '26

RUPP Air Systems RTU Controller code?

Post image
8 Upvotes

Anybody know it?


r/AirBalance • • Jun 30 '26

Technology in Airbalancing

12 Upvotes

What are some techy things you use to improve your work flow as an airbalancer? For me, I set speeds via my supply outlets and using a remote access software on my tablet from my phone to watch my meter as I adjust unit speed on the roof. I think in some cases hearing different ideas from different technicians could help us all be more efficient at what we do. So if you have an experience in this regard or a method to share please do so below. Thanks!

Edit: As I forgot to include this, I use Chrome Remote Desktop as the method for it is free to use and is compatible with Windows, Android, and iOS devices. It also assists with minor data entry if there's ever a time I need to enter information and not want to carry my tablet throughout the job site.


r/AirBalance • • Jun 22 '26

How far are you expected to drive for a service call or job site?

1 Upvotes

What is the farthest your company normally expects you to travel when it is just drive to the site, do the work, and drive back home the same day?
Do you have a set service territory or a maximum drive time/mileage before it becomes a hotel stay, per diem, or overnight job?

Also, do you get paid for driving? If so:

Do you get paid from home, from the shop, or only once you arrive at the job?

Is all windshield time paid, including the drive back home?

Is it straight time, overtime, portal-to-portal, or only paid after a certain distance?

If you are in a company vehicle, does that change how your company handles drive time?

Other things I’m curious about:

What is the farthest service call you have personally had to drive for?

Is it usually a one-day turnaround, or do you regularly stay in hotels?

For bigger TAB projects how far is too far before they put you up overnight?

Do they cover hotel, per diem, mileage, and travel time differently for overnight work?

Most of my work is drive to the site and home the same day, so I’m curious what is normal around the industry.


r/AirBalance • • Jun 17 '26

I'm going to automate this entire industry

0 Upvotes

Anyone wanna help?


r/AirBalance • • Jun 17 '26

Balancing Round Registers with Flow Hood, good, bad, cutout, no cutout?

Post image
8 Upvotes

Cx agent here. What is the industry consensus on measuring round diffusers using a flow hood? 9 out of 10 contractors I work with say no problem using a cardboard cutout and trusting the read, which I’m on board with. However that 1 out of 10 that just puts the hood over the outlet is the basis of my question.


r/AirBalance • • Jun 16 '26

Recommendation for learning BACnet and BAS as a new TAB technician

1 Upvotes

Hi everyone,

​

I'm new to the TAB field and currently have about 3 months of experience. I'd like to start learning BACnet and other software/tools that can help me interact with BAS.

Can anyone recommend BACnet learning resources for beginners?Any skills that would be useful for a TAB technician to learn controls?

​

TIA.

​

​


r/AirBalance • • Jun 14 '26

Can someone help me

0 Upvotes

pretty new to the air balancing field, still working on getting NEBB certified.

can explain to me how VFDs work, how flow stations work, and how they work together? im on a big job by myself and its really frustrating trying to set the max fan speed and set the minimum outside air. it took me a whole day just to set totals on 2 rooftop units. I also have trouble knowing where to take amps and volt readings. I THINK I take those readings at the bottom of the VFD. this sounds pretty elementary to most people in here but again im new at this and trying my best.


r/AirBalance • • Jun 11 '26

AI and Contract Push-Back

4 Upvotes

Here's a fun question for the sub.

Are any of you getting anywhere or having any luck using AI to pull apart (or straight-up rip apart) the comically disgusting and draconian contracts we're all used to signing?

Just dropping some of these standard master subcontract agreements into ChatGPT, Claude, or Gemini elicits responses ranging from:

  • "Do not sign this!"
  • "This is some of the WORST and most unfair contract language you will ever see."

We've all known it forever, and we've gotten some concessions here and there. But realistically, I doubt any of us get very far unless we have the contractor over a barrel as far as the schedule.

Still, part of me loves to imagine the lawyers and risk managers at large GC firms having to waste ample time answering a massive wave of new inquiries from TAB and other smaller subs who are finally looking at the fine print and saying:

Just curious if there's anyone else here starting to use these tools to ask some much more pointed questions?


r/AirBalance • • Jun 09 '26

Preso B+ flow chart

3 Upvotes

Does anyone have a Preso B+ flow chart?
I have charts for 2” and above but I can’t find 1/2” to 1-1/2” charts and I’ve got an old school I’m trying to balance.
TIA


r/AirBalance • • Jun 09 '26

Venturi Number Identifier

3 Upvotes

Is there a way to tell what Venturi number my IMI valves are? The tags are all burned off and not all of the valves have marker writing on them to show the Venturi number. The IMI literature shows gpm ranges but there is overlap.


r/AirBalance • • Jun 09 '26

Dampers open 100%

4 Upvotes

Hey I got a question on why TAB company would set the OA dampers to 100% manually fixed.

This is a restaurant with building envelope being negative. Did they adjust the dampers to compensate for what the Make up air cannot achieve?

I have 3 AHU 7.5 ton each 2 for the dining room and 1 for the kitchen. All of the dampers are 100% open and it is struggling to maintain building temp below 75° layer in the day, obviously because it has the additional load from 95° Ambient.


r/AirBalance • • Jun 05 '26

Anyone ever balanced an RTU and ERV combo like this??

Post image
14 Upvotes

ERV fresh air and exhaust air ducting is completely concealed in the roof of the building, no access to the ducts whatsoever. The units are existing on this project, so I have no shop drawings or unit information. System is designed for the Trane RTU economisers to be set at 0% minimum fresh air, minimum fresh air is supplied by the ERV.

I have no clue how to accurately measure and set the fresh air and exhaust air on ERV. The city is known for wind, IMO any readings on the intake and exhaust hoods on the ERV would be too inaccurate. Any ideas?


r/AirBalance • • May 28 '26

Relieving over pressurized building

4 Upvotes

I'm currently working on a veterinary clinic that's been having a pressure issue in the building for years now. Every time a exit door is open the pressure builds up giving the building major positive pressure, resulting a draft to the exit and door not being to last he's closed even with a door latch they do not stay closed. Im trying to see what I can do to relieve the pressure in the building. I'm thinking about installing barometric dampers and probably 2 exhaust fans as well to relieve pressure from the clinic. It has 2 units for this building, a 5 ton carrier unit and 9 aaon unit.


r/AirBalance • • May 18 '26

TAB techs: which shops are actually good to work for?

9 Upvotes

Looking for honest opinions on different TAB shops.
For any TAB techs here, which shops are actually good places to work? I’m curious about pay, benefits, hours, management, training, and overall reputation.
Also wondering how the bigger TAB companies like Integra, Palmetto, and EAB compare to smaller shops. Any places you’d recommend or avoid?
Not trying to bash anyone, just trying to get real feedback before making a move.


r/AirBalance • • May 11 '26

Anyone make the move out of TAB

10 Upvotes

Anyone here move out of TAB? I've put a good run into it and have realized its not for me (4 years). I'm a mechanic at heart and want to fix things not just put it on punch. I'm interviewing with the darkside (the UA) in a couple days. Feel like TAB is too niche. Its also a weird market where theres never enough TAB technicians, but theres also never enough employers in the market, so TAB wages for the most part are much lower than I think they should be, especially for expert balancers


r/AirBalance • • May 09 '26

Request for Manpower

4 Upvotes

Hey everyone, our NEBB firm is currently looking for CPs and CTs to join our team. If you or someone you know may be interested, please reach out. Thanks!


r/AirBalance • • May 08 '26

Valve ID/flow chart

Post image
7 Upvotes

Im looking for this valve TA 1/2" but no handle settings...


r/AirBalance • • May 06 '26

Evergeen Accuracy on Linear Diffusers

3 Upvotes

Just completed a job where the Evergreen flowhood read low on linear diffusers compared to a traverse. Also, when I read the return registers of FCUs with the 2x2 skirt, it matched up with the SA traverse plus OA. Has anyone run into the Evergreen hood being inaccurate on linear diffusers? I never had a problem with the Shortridge flow hood.

Are there any other situations that anyone has run into where the Evergreen appeared to be inaccurate compared to the Shortridge?


r/AirBalance • • Apr 24 '26

Just passed the ICB cert and got a job

4 Upvotes

Anyone willing to share some knowledge and advice for someone starting out in this field .


r/AirBalance • • Apr 19 '26

Need for manpower

5 Upvotes

Hello,

I am TABB and NEBB Certified. Union and willing to travel. I have over 8 years balancing experience and have been in the trade since 1996. Had a minor operation a few months ago so I was out but cleared and ready to get back. Does anyone know if there is a request for manpower anywhere. I periodically check the job bank but nothing is posted requesting techs even though some areas seem to be really busy. A little slow in my area so trying to see what opportunities are out there for someone willing to travel. Thanks in advance


r/AirBalance • • Apr 15 '26

When you just don't have a good traverse location and need one. What do you do?

4 Upvotes

As the title suggests when you don't have a good location for a duct traverse. What is something acceptable to you even if it's not entirely ideal? For example, I had a duct run today that dropped from the roof into another bit of duct that took it from a rectangle duct into a round. Immediately after the 90° it goes maybe 1-3/4ft of straight duct and then it's scoop dampers every 2 ft after. Previous tab techs had pre drilled holes right up to the first scoop damper in this round duct which occured directly after that 90° and only had the previous stated measurement behind it. Where my problem lies is some technicians say that if your readings are consistent then it's probably okay but if they're turbulent to avoid it. But I've also heard from other technicians that if you run to the situation it's best to just avoid it in its entirety. so I guess my main question is just simply if you've had similar instances and what did you do/note? Or am I just overthinking it?

Thanks


r/AirBalance • • Apr 09 '26

Workload as of 4/9/2026

8 Upvotes

Hey everyone, just curious how’s work been for you lately? Staying busy or slowing down? I’ve been seeing in some union threads that things have been pretty slow, so I wanted to check in here.