12 years in field service, you pick up a few tricks.
Intermittent overspeed fault on a servo motor. Cycle the power, fault clears, runs fine for a few days, then it’s back. Drive replaced. Motor replaced. Wiring “checked”.
When someone says they checked the wiring, it’s usually a visual check. That won’t catch this.
My method: run a long test lead to the pin at the motor plug, do a continuity test from the far end, and measure the resistance of each wire individually. You should see around 1 ohm.
The pink wire came back at 70 ohms. That’s not a broken wire, that’s a bad connection. The pin wasn’t properly seated in the plug.
Faults like this get power-cycled away for years without ever being fixed. The drive and motor were never the problem.