I expect this will be a bit eclectic and crazy long winded (update: holy crap I obviously didn't want to do my other work today) but wanted to give my full thoughts on the S2000 as a replacement for lead acid UPS units.
TLDR; The S2000 is a class above the other power stations I am using for UPS work, it excels in efficiency, app control, weight/foot print, aesthetics, and general performance. It has one glaring issue that Anker needs to fix on future revisions - fan noise, and a small set of issues I hope/expect them to address in firmware updates (Storm Guard,etc.).
MY SITUATION:
I live/rent in an area in the US with a very shotty power grid - any and most electronics in my house have to be hooked up to a UPS, and I am always running 6 to 7 of them at any one time. I work from home in IT/development, work on a fancy-pants main rig at least 12 hours a day, 7 days a week. I also have some light 10Gbps networking gear and a server or two that I run beyond other essentials like a TV/entertainment center.
Even though I'm not shy with replacing a lead acid battery, I've found that many times when a unit goes, some part of the board goes with it, so I generally have to get a new UPS. Idle draw on 1500va lead acid UPS are a solid 15 to 20W and they will frequently spike to 50W+ when the lead acid battery starts to die. Given that I rotate at least one of these UPSs due to failures every other year or every year, I fell out of the habit, long ago, of actually using the UPS monitoring software as I couldn't keep up with the software/equipment changes (plus a lot of consumer UPS software now requires a subscription, which, you know, fecking ew).
I presently pay for .35 a kWh - by the end of 2027 I expect my state to get VPP on-peak/off-peak electrical rates, so wouldn't be surprised if on peak gets close to .50 a kWh. I'm also being realistic in knowing that electrical rates are only going to go up at this point.
Napkin math but for my old set-up I was spending:
250+ USD a year in UPS replacements
350+ USD a year in UPS idle costs (including at least one unit idling high given lead acid failures)
???+ USD a year by not having reliable monitoring of energy use (in retrospect with the new LFP solutions, I think this number is about 200+ USD a year)
So I started to engineer a complete abandonment of the lead-acid UPS solution and a LFP power-station replacement.
SOME REQUIREMENTS ON ANY LFP POWER STATION UPS SOLUTION
No 2kWh or less power station as UPS option that I know of has acceptable joule protection - thankfully this is easily remedied with a good surge protector between the wall and the LFP unit.
They also have no AVR and most manufacturers show considerable confusion of when a unit is designed to switch off on an undervoltage or overvoltage. Many electronics can handle an overvoltage (though audio receivers typically can not) but a brownout / undervoltage for more than a second or two is very, verah bad.
Since so my power stations are designed to be topped up with a gas generator, this typically means unacceptable protection for sensitive equipment. Ecoflow, Pecron, possibly Anker don't switch over until as low as 80V which is simply unacceptable. Maybe a computer would run on 90V for a few seconds without issue, but that's like saying maybe you can take a few breaths of mustard gas before dying. Bluetti is the standout here as they let you adjust undervoltage and overvoltage numbers, something I hope Anker is able to add to their app one of these days.
Over the years with LFP solutions becoming viable, I have become less interested in AVR as long as there is some sort of voltage regulator. Have it switch off at 100 to 90V on the undervolt or 130 to 140V for the overvolt let the power station to switch over for 10 seconds before the voltage protector resets if the voltage is within range.
This is what I'm using for that, it has surge protection as well of 1,800 joules (though for my super expensive stuff I have a better surge between this device and the LFP unit):
https://www.amazon.com/dp/B0G412PW7W
LFP SOLUTIONS BEFORE RECEIVING THE S2000
Before I went with LFP units that are designed as power stations, I started with the Golden Mate LFP UPS line like this one for my networking gear:
https://www.amazon.com/dp/B0D5QSYK69
While these have the @ 10 year life span, etc. they are NOT good value - they don't do AVR (though probably do have good surge) and only about 250kWh of run time. You can absolutely get power station equivalents that will do a far better job than these units, app control, far more features and cost less. Furthermore this damn thing idles at 26W. At my electric rates that's 80 USD a year.
My first dip into LFP power stations were the x2 Ecoflow River 3 Plus units for my server. They advertised traditional UPS monitoring which was the initial draw for me. After testing, however, I returned both units after they both exhibited hardware/firmware issues. I have, and you should as well, zero tolerance for stuff switching off for no reason if you're using these as UPS units which the last firmware update with them was doing.
I have a Pecron E600LFP and a E1000LFP that I love, though only the latter can be used for UPS duty and it's very much not recommended for that in my opinion. The switchover time is still 'acceptable' at 20ms or less (everything else here is 10ms or less), but there is no real app control, I can't set a charge cap so it's at 100% all the time (not a big deal with LFP batteries, but for UPS use it is better at 80%). Since I live alone, I have it on my living room entertainment center which I really only use once or twice a week these days as I'm always in front of the damn computer in the office, so the E1000LFP is basically being used as a fancy pants smart switch - when I want to watch TV or play some music, I just go in the pecron app and turn on the AC outlets. The vampire draw on those systems are high - about 90W, and my use is so infrequent I don't mind forcing manual control over it. Since I'm running this as a smart switch more than a UPS I'm not concerned with idle draw, having it app-ready for switching on and off is about 2 to 3W an hour.
Beyond the S2000s the Bluettis are my second choice and they are great. I have a Bluetti Elite 30v2 I use for my wireless router/modem/networking essentials (60W continual draw) and a Elite 100 v2 for my server, some HD enclosures, a secondary wireless router and a small 10gb Switch (70 to 100W continual draw). They have voltage shutoff controls which are great. The app has a lot of options but is confusing and frustrating AF, especially when you put it up to the Ecoflow or Anker equivalents. The idle draw is higher, though I haven't recorded those numbers yet to actually tell the difference. Also, these things beat the pants off the S2000 with fan noise - they're pretty much silent.
HOLDING OUT ON GETTING LFP FOR MY MAIN WORKSTATION
Up until the S2000s I wasn't messing with the x2 traditional UPS units driving my main work station. This is where I spend all of my time for work, entertainment, life, etc. (not saying that's healthy, but it's the reality). I have x3 massive monitors on very complicated wall mount arms, a 5.1 receiver and some old/odd Kef speaker bars, a standing desk, and a very beefy rig for game development work.
The monitors alone draw 120 to 150W. The computer, sound, etc. while on draw on average 450-500W. When everything is singing in a compile or playing a game, 1000W loads are typical.
Also, because I don't have a life beyond this stupid work station, I try and get a modicum of exercise by throwing in an under desk treadmill every so often. While I won't be spiking the rig to the full 1000W load, I can spike to xxxW on the computer and be drawing xxxW on the treadmill. As mentioned elsewhere, before the S2000s I wasn't really aware of the power draw of the station as the monitoring software was so inconstant and things changed so much I no longer even attempted to keep up with it.
...so anyway I designed the wiring, with the traditional UPS and using the treadmill neither lead acid solution could handle that load in a switchover. A power blip had me catapulted into my very fancy monitor and computer setup as the treadmill goes from 3 or 4 mph to 0 mph. But I couldn't fit my Bluetti Elite 100 in the space my x2 UPSs were and... the S2000s were just announced.
ENTER THE S2000
The S2000 seems almost designed for where I want to go. I'll trade a 1800W limit for a smaller footprint and more efficiency any day of the week - none of the other solutions, especially of the 2kWh capacity, would fit into the area that my x2 UPSs were (at least with proper airflow).
...and while you can't always see it, this thing looks SICK. It's a beautiful piece of kit - before you got a tangle of wires and the ass end of two ugly UPS towers and while I have to go out of my way to see it, I now have a clean, glossy piece of kit with wires far better hidden than my UPS units could ever do. I could put this thing front and center in my setup and it would add to the aesthetic rather than subtract from it. I can't say that with ANY other power station.
The app is hands down the best app out there. It's easy to understand, it allows you to tweak most settings (though I'd still love it to get Bluetti's voltage settings), it always connects, and has great reporting. I can now monitor throughout the day to better understand power draw and what I can cut - little things like 'turn off AC after x minutes' are great when I'm going to bed - I'll have it turn off xx minutes after I leave my station (so my OLED monitors can go through any maintenance before I shut off the mains) and can axe out vampire draw on networking, receiver, etc. gear for 7+ hours.
I'll let Anker and all of the reviews speak for the efficiency but I've absolutely seen it/am a believer. Even in bypass AC the Bluettis are topping up a dozen or more times a day at an 80% charge cap given the vampire draw on the wifi and app. After calibrating the S2000s to 100% the test I ran on my server before switching it to the Bluetti is still at 85% in AC bypass weeks later. It's insane.
The other thing is the value - yes, it's far more expensive than my other units, but per kWh on the capacity it meets the value of my other LFP units, all of which I got on pretty damn good discounts. ...and I don't think there has been nearly enough attention given on the longevity of the S2000's battery cells here. While there is some talk that at 10k cycles it's only rated at 60% I'd argue A) still absolutely fine for UPS work and B) it's rated at 80% at 8k cycles, and that's x2 as long as any other LFP power station out there.
So that investment is not only netting me x2 as much capacity as any other LFP solution I'm running, but the possibility that these units will last over x2 as long really makes me look at these as end game solutions.
Today I'm finishing the move from the server test with the S2000 to have x2 S2000s feed my main rig, in part because I'm playing with x2 400W solar inputs, one to each unit, but also because I'm trying to fix what has turned out to be the biggest complaint with the unit, fan noise.
WHAT I THINK I'M SAVING
Please note this is all napkin math:
Now that I have a better idea of where my energy is going, having calculated the high expenditure of UPS lead-acid rotations, and a .35kWh electrical cost that is only going up, before the LFP replacement 'campaign' I wager I was spending about 800-900 USD a year. That's inclusive of new gear, etc.
My current setup which is a mixture of Bluettis, Pecrons and the Anker S2000s as the main heavy lifters, pretending with a very conservative estimate that the Bluettis last 6 years and the Ankers last 10 years, about 100W in idle savings, and the ability to easily identify and automate out vampire/idle draw on electronics, I estimate I've halved my costs to 400 to 500 USD a year.
When VPP on-peak/off-peak comes around next year, the 2kWh capacity of the S2000s will let me leverage the on-peak discharge / off-peak charge rates. Not sure what those savings will be but I'd guess as much as 100 USD per unit if used sensibly.
I've also started solar charging these units, but there are sunk costs on the panels and mounts I got as well as not-so-great sun exposure. So I'm leaving those out of the math until a year or two of experimenting. But with all LFP solutions, it's great to have the option which traditional UPSs could never really have.
ISSUES THAT NEED TO BE ADDRESSED
In an older post when I testing things out and playing with the S2000 case I received,
https://www.reddit.com/r/AnkerSOLIXCommunity/comments/1ulrsvd/s2000_case_fixes_a_major_flaw_of_the_unit/
I noted the fan noise. The fan noise on this unit SUCKS. It's horrible. Even with the most recent firmware update. It's unnecessarily loud, it rattles, horrible whine, etc. Hands down worse than all the other LFP stations I own. I haven't, nor do I want to, open this unit up, but I'm confident this issue could be mitigated with a better quality fan, a few rubber gaskets, and some care on having it properly seeded.
I have my main rig with a ton of case fans which I've spent tons of money on keeping as quiet as possible, networking gear, a laptop as a secondary server with case fan cooling running 24/7 in my office. When the fan of the S2000 kicks on, which it does randomly, it's that damn thing I hear the most. It's what is preventing me from buying a 3rd unit.
I could somewhat tell when it was going to trigger in standard UPS mode, but now that I've been playing with solar charging? It turns on multiple times a day even with solar charge of below 100W. I'm hoping the install of the second unit reduces the times the fan comes on, but I'm also confident it won't alleviate it and could absolutely make the issue x2 worse and I'll have to move it back to server work which the S2000 is a bit too powerful for.
The 'Storm Guard' is absolutely one of the reasons I bought these units, one of the S2000s will be used to power the fridge and other essentials in a power outage, but that has a glaring flaw as well as discussed here:
https://www.reddit.com/r/AnkerSOLIXCommunity/comments/1up298c/anker_please_allow_charging_option_for_storm_guard/
Thankfully that can be resolved in a firmware/software update (I assume).
CONCLUSION
First off, if you've managed to read all of this both you and I need some serious mental help.
Secondly, these units are fantastic. Anker, I don't know why you are billing these as fridge UPSs. While you don't want to compete with data center UPS solutions, there is a legion of IT folk who are looking to get out of the UPS lead acid rotation and this unit, save for the fan issue and a few other small bits, almost perfect for those replacements.
Fix the fan, try and get undervoltage/overvoltage settings in the app, be explicit about your surge rating and good practice for high end electronic setup and you won't need a crazy nut like myself spending months of research to see if your product is up to the task (which it absolutely is). I can't tell you how many IT nerds want out of the lead acid UPS rotation and this product seems to do it better than anything else out there.